Quomodo AC Hipot test intentione pro diversis instrumentis determinatur?

 May 18, 2026

 Aliquam nuntium

 

Quid est basis ad eligendam intentionem pro AC Hipot examinis?

Test intentione determinatur ab apparatu scriptor gradu insulationis aestimatae (Um, BIL) et vexillum productum - applicabile nulla est intentio universalis.

 

Delectatio per apparatum genus intentionis:

Apparatus

Standard

Test Voltage

Duratio

Virtus Transformer (Um Minus quam vel aequalis 72.5 kV)

IEC 60076-3

1.7 Um / 3 (adductus) + PD

30 test{1}} min apud Um/√3

Power Transformer (Um> 72.5 kV)

IEC 60076-3

1.7 Um / 3 (brevis{2}} durationis inductae)

60 s

Distribution Transformer

IEC 60076-11

2.0 rated voltage

60 s

Potentia Cable (MV)

IEC 60502-2

2.5 × U₀

30 min (suscipere) / 60 min.

Potentia Cable (HV)

IEC 60840

2.0 × U₀

60 min

GIS / Switchgear

IEC 62271-1

1.2 Um

60 s

Bushing

IEC 60137

1.2 Um (PF test)

60 s

CT

IEC 61869-1

1.3-1.5 Um/ √3 (adductus)

60 s

 

Ductor campi practicus:

• Semper nominatus consulas (list Um, BIL).

• Reducere intentionem per 80% ad campum probatio instrumenti vetusti (IEEE 400,2 pro cables).

• nameplate numquam excedunt BI.

• Comproba vexillum producti antequam voltage - transmutator vs funem voltage eligens differt in eodem genere.

mitte Inquisitionis