Q: Homines vocant TDR "Cable Radar." Quomodo sine fodiendo culpam invenit?
A: TDR pulsus volgus humilis- (<100V) and listens for the reflection. Any impedance change causes a bounce-back wave.
Quam legere TDR screen:
|
Waveform Shape |
Meaning |
Culpa Type |
|
Supra (positivum) |
Impedimentum → infinitum |
Patefacio Circuit / Cut cable |
|
deorsum (negative) |
Impedimentum → Nulla |
Circuitus brevis / Phase- Terrae |
|
Flat unda |
Impedimentum est Constant |
Sanus cable |
Logica: Distantia=(velocitas Time) / 2. TDR invenit "breves mortuas" et "filias fractas" facile.
Quid est "Thumping" (High Voltage Surge)?
Q: TDR fune sanum ostendit, sed ruptor supplantat. Cur obstreperetur?
A: TDR non potest "videre" altum- resistere rimas insulationis. Arcum artificiosum in situ culpae creare opus est.
Thumping processus:
1. Praecipe: Equipment gravem altam voltage capacitorem urget (Thumper).
2. Dimittite: Solvit industria in unum pulsum magnum (eg, 15 kV) in funem.
3. Arcus: Pulsus defectum ferit et Arcum artificialem creat (Flashover).
4. Signum: Arcus brevem temporalem agit, undam TDR reflectens.