Q: Datum P₀ et Pₖ ex probatis, quomodo efficientiam computamus in diversis gradibus oneris?
A: Efficientia η=P_out / (P_out + P₀ + ² Pₖ) × 100%, ubi {{6} elementum onus.
Exemplum: 10 MVA commutator, P₀=12 kW, Pₖ=85 kW:
|
Load |
|
Output (kW) |
P₀ (kW) |
Pₖ (kW) |
η (%) |
|
25% |
0.25 |
2,500 |
12 |
5.3 |
99.31 |
|
50% |
0.50 |
5,000 |
12 |
21.3 |
99.34 |
|
75% |
0.75 |
7,500 |
12 |
47.8 |
99.21 |
|
100% |
1.00 |
10,000 |
12 |
85.0 |
99.04 |
|
120% |
1.20 |
12,000 |
12 |
122.4 |
98.89 |
Maximum momentum ad=√(P₀ / Pₖ)=0.376 → ~37.6% onus.
Energy signa efficientiae;
• IEC 60076-20 : EEI CLASSIS A (summa) → D.
• EU Ecodesign 2019/1783: Tier 2 (2021), Tier 3 (2025-27).
• DOE 10 CFR Pars 431: Nova regula efficax mensis Iunii MMXXVI.
• GB 20052-2020 (Sina): Gradus 1 (summa) → III.
• IS 1180 (India): APES astrum Rating 1-5.
TCO accedunt: TCO=Pretium + A P₀ + B Pₖ
A ≈ $3,000–8,000/kW (nullo onere capitalismi - sumptus).
B ≈ $500–2,000/kW (onus capitalised sumptus).